Emergency Elevators

In non-residential buildings with a building height of more than 51.50 m, at least 1 elevator will be arranged as a fire elevator for use in emergencies. A fire safety volume must be created on each floor for these elevators. The cabin area of ​​the emergency elevator is at least 1.5 m², the carrying capacity is at least 630 kg, its speed will be at a speed that will reach the top floor in 1 minute from the ground floor, and it will be powered by a generator that will turn on automatically in case of power failure. .Emergency elevators will serve every floor and will be usable normally. The doors, electrical installations and cables of these elevators will be resistant to fire for 2 hours. The installation inside the elevator shaft will not be affected by water. Emergency elevator shafts will be pressurized

This elevator is installed to be fed from an uninterrupted power supply.